TLD-1™ Line Testing

TLD-1™ Line Testing

The TLD-1 test is a Pressurized Dispensing System Tightness Test, 3rd-party certified to meet and exceed the requirements of the U.S. EPA certified performance standard detection leak criteria of 0.38 LPH for line system tightness testing. The procedure for this hydrostatic testing using pressurized nitrogen is to isolate the product line from the tank or STP in the manway turret, and apply nitrogen through an impact valve test port at the dispenser island.

Highly trained technicians hold valid Tanknology Certificates of Training for the TLD-1 Pressure Line Test Certificate Exams.

TLD-1 Line Testing Features

Precision Technology for Accurate Leak Detection

  • Patented technology for both pressure and suction line testing at 1.5x operating pressure.
  • Positive nitrogen pressure is applied with a probability of leak detection at 99.7%.
  • Maximum Certification Capacity: Rigid piping 652 Litres, Flexible piping 450 Litres.
  • Hydrostatic testing Pass / Fail criteria is dependent upon a Certified Leak Rate 0.38 LPH.
  • Average test data collection time 45 minutes.

How does TLD-1 Line Testing work?

The procedure for the hydrostatic testing of both pressure and suction line systems is to isolate the product line from the tank or STP in the manway turret.

Positive nitrogen pressure is applied at 1.5x operating pressure. ONLY after recording two consecutive readings that meet the pre-established threshold GPH (Gallons Per Hour) is the line declared to be tight and passing.

Why would I want to use the TLD-1 Line Test?

TLD-1 hydrostatic pressure testing is proven technology for accurate leak detection on both pressure and suction lines, certified by the U.S. EPA, reliant on a certified leak threshold.

The line test provides minimal business disruption to operations and only the product line being tested is required to shut down. All other product lines may operate normally dispensing fuel.

Testing time is usually limited to one hour approximately per line.

What report do I receive from a TLD-1 Line Test

The line test report provides a detailed record of the test for compliance purposes. It will document the condition of your product line, or line system via a clear Pass or Fail.

If a leak or other issue is identified, the report provides recommendations to meet ongoing compliance.

Benefits at a glance

Helping you meet strict regulatory requirements with U.S. EPA certified industry-leading testing technologies.
Efficient, accurate precision line testing that reduces forecourt downtime, ensuring minimal disruption.
Researched and developed by Tanknology Australia, the VacuLine test allows hydrostatic suction line test Fail results to be confirmed using a partial vacuum. With this confirmation, complete confidence in the test results will ensure peace of mind re any rectification works required on the product line.